1.6 Adjuster code 1
Adju-
ster
Hy-
draulic
Function Setting
range
Factory
setting
Unit Basic setting
Dat.:
Revised
Dat.:
04-06 all Hydraulic variants 1÷1 1 -
Hydraulic variant
1 = Speed (rpm) controlled collector pump on tank (SP) 1
04-20 all eBUS-Addressing 1÷16 16 -
Only ES 5911, not in use:
Addressing the controller in eBUS combination. 16 standard master addresses.
04-36 all eBUS-charging on/off off -
Only ES 5911, not in use:
On = eBUS charging by solar controller activated
Off = eBUS charging by solar controller deactivated, is carried out by another controller in the eBUS combination.
05-04 all Legionella protection temperature 60÷80 60 °C
Set value for the thermal pasteurisation (Legionella protection). Tjis is the temperature at which heat treatment of a
water store as a contra legionella takes place.
Not in use!
05-14 all Legionella protection function 0÷9 0 -
You may specify when and how often the legionella protection function is carried out.
(protective temperature as per Adjuster 5-04)
0 = never
1 = Once each week
8 = Once every day
9 = Always
Not in use!
08-01 all Increase collector tank for charging ON 0÷50 15 K
If the temp. at the collector sensor is higher than the temp. on the tank sensor + set value "08-01" solar charging is
enabled.
08-02 all Increase collector tank for charging OFF 0÷50 5 K
If the temp. at the collector sensor is less than the temp. at the tank sensor + set value "08-02", solar charging is
disabled.