8.6 Flow settings:
The ow regulator should be set to 0.5 to 1.0 litre per minute per panel. A three-panel
installation is set to a ow rate of 1.5 to 3 litres per minute.
How to read the ow setter:
8.7 Pressure settings:
The maximum pressure is 6 bar. Once the system is pressurised keep the pressure
between 3 – 4 bar. With higher pressure inside the system, the glycol/mix will not
evaporate until temperatures of around 120°Celsius are reached. Pressurisation
therefore helps to prevent glycol degradation and enables more useful heat energy
to be applied.
8.8 Maintenance:
The double pump station does not require maintenance. It is fully controlled by the
digital controller. The customer should do a visual check every month for leaks,
signicant different readings on the temperature gauges and readings on
digital controller, pressure drop below red line on the pressure gauge can indicate a
leak on the system. The customer should be informed that uctuations in pressure
readings while the system is operating are perfectly normal. In case of any
unexpected changes, the customer must contact the installer immediately.
Note: A competent solar engineer should service the system 3 years after install, and
then every 2 years there after.